Fire riser room requirements california.
In california all sprinkler water must go to sanitary to be treated before going to the ocean.
Page 1 of 2.
The fire sprinkler riser shall be located on the outside wall between 12 and 18 from that outside wall and at least 12 from any other wall.
The fire equipment room shall be used for fire protection equipment and controls only.
Fire pump and riser rooms shall be maintained to be no lower than 40 degrees fahrenheit with the heating device permanently installed.
Water enters the building and goes through the backflow preventer and then into the fire pump both being located in the fire pump room.
Title 24 part 2 section 2 3303 i 1 and i 2 exception.
On the first floor there is a floor control valve with drain.
Where a door opens over a landing the landing shall be at least as wide as the door and at least 5 feet long.
This could be accom plished using a key box as provided in section 506 1.
The minimum size of the equipment room shall allow adequate firefighter access and mobility with the following minimum clearance requirements.
Where the door opens into the stairway of a smokeproof enclosure the landing need not have a length of 5 feet.
Permanent artificial lighting is now required to be installed by the 2018 ifc ibc.
One side may be a minimum of 18 inches from a wall.
2018 fire code expands requirements.
Fire control rooms shall have a minimum dimension of 5 and not be less than 35 square feet in usable area.
The temperature in the room must be maintained at 40º fahrenheit or higher to ensure the piping and components do not freeze.
Permanently installed artificial illumination shall be provided in the automatic sprinkler system.
Automatic sprinkler system riser rooms and fire pump rooms shall be maintained at a temperature of not less than 40ºf.
Where provided fire pump rooms and automatic sprinkler system riser rooms shall be designed with adequate space for all equipment necessary for the installation as defined by the manufacturer with sufficient working room around the stationary equipment.
Fire pump and fire sprinkler riser rooms must be readily accessible at all times but can be locked if a key is available.
Into the fire equipment room.